The MEAC offers continuous acquisition, evaluation, storage and visualization, as well as transfer of emission data for modern emission data management. Up to 16 data acquisition units, each equipped with a scalable ring buffer, can be connected to the central Emission-PC. It is also possible to integrate process control systems. MEAC is TÃœV approved and certified. The MEAC2012 version is designed to meet German legislative requirements, while the MEAC2000Â EU complies with European directives and regulations.
At a glance
Evaluations according to 1, 2, 13, 17, 27, 30, 31 BImSchV and TA Luft |
Analog and digital data collection saved at 5 s/1 min intervals with auto-backup |
Distributed visualization, operation in the network and automatic e-mail alarms |
Flexible data presentation also in process images |
Analog and digital data to the customer system at 5 s/1 min intervals |
Recording of QAL3 cycles |
Your benefits
Time savings through simulation mode for installation and functions checks |
Savings on service costs through flexible parameterizing interface for users, e.g for device calibration |
High availability through automatic synchronization service for data and parameters |
Parallel calculation of greenhouse gas emissions in the same system |
Fewer limit violations due to special CO evaluation |
User can draft own reports in MS Excel format, to which data are then added automatically |
Customer network can be used to connect to process control systems, no need for new cabling |
Continued use of existing data and parameters from earlier MEAC versions |
Fields of application
Acquisition of measured and operating data for continuous emission monitoring |
Data preparation in compliance with legislation |
Free customized and legislative reporting |
Data transmission rate to authority |
Technical data | |||
Ambient temperature: | MEAC data acquisition unit: 0 ... +50 °C | ||
Ambient humidity: | MEAC data acquisition unit: 0 ... 95 % relative humidity; non-condensing |
||
Conformities: | 1999/13/EC 2000/76/EC 2001/80/EC 27. BImSchV 30. BImSchV |
||
Electrical safety: | CE | ||
Enclosure rating: | MEAC data acquisition unit: IP 20 | ||
Analog outputs: | 8 outputs: 0/2/4 ... 20 mA, 500 Ω max. 4 boards (32 analog outputs) per data acquisition unit |
||
Analog inputs: | 16 inputs: 0/2/4 ... 20 mA, 100 Ω, -10 ... 10 V max. 5 boards (80 analog inputs) per data acquisition unit |
||
Digital outputs: | 12 relay contacts: 48 V, 500 mA max. 8 boards (96 relay contacts) per data acquisition unit |
||
Digital inputs: | 32 optical coupler inputs 48 V DC, 150 mA max. 8 boards (256 digital inputs) per data acquisition unit |
||
Interfaces: | RS-232 for Emission-PC, service or printer RS-485 for Emission-PC |
||
Operation: | Via Emission-PC and software MEAC | ||
System components: | MEAC data acquisition unit Emission-PC Software MEAC2000 |